Project Describtion Parallel Operation Switching Devices   PLC Matlab

مواقع مفضله بحث سجل الزوار شكر وعرفان من أنا

operating outside of the nameplate rating:

Most generator can be operated with a voltage-variation of 5 percent above or below rated voltage and still safely carry rated KVA at rated power factor. However, the manufacturer should be consulted if deviations greater than 5 percent are anticipated. If the generator is to be operated frequency, a proportional decrease from rated voltage and rated KVA is required. Although a reduction in operating frequency of up to 5 percent of rated is not harmful the manufacturer should be consulted.

 

Under emergency conditions it some times becomes necessary to operate a generator in excess of its rated KVA. Because the increased load causes increased heating of the armature and field windings. Additional cooling must be provided to prevent damage to the machine. In the case of selfcontained air or gas recirculation systems, an increase in the flow of cooling water or other coolant will help keep the temperature down.

 

However, under no circumstances should the temperature of the air or gas be allowed to reach or go below the dew point; temperatures below the dew point cause conderrsation of any entrapped moisture on the windings of the machine.

 

The accessories wanted for parallel operations.

(1)-Paralleling unit Aplication

 

This unit is normally used for switching in parallel generating sets with either the mains supply  or with other generating sets Sub position for switching in parallel are    

1-coincidence of the phase

2-equall voltage

3-equall frequancy

synchronising unit is mmonitoring these values and gives an output impulse ,when they are within their pre-set limits

manual synchronization by possibly unskilled personel is dangerous and can result in damage of the equipment it is therefore recomendable to use an automatic synchronizing device .

frequancy equallization can be made as follows:

1-by manual adjustment of the soeed governer  motor

2-automatic frequancy adjustment using frequancy control unit.

 

after switching in parallel start loading the generating sets:

 

1- by manual adjustment of the soeed governer  motor

2-automatic load equalization with the load balancing unit this unit gives output impulse for the speed of the governer motor to balance the effective power to tow or more generating sets in parallel  Function

The synchronizer unit is supplyed from one phase of each system .the unit compares the two frequacies, the difference in voltage and measure the phase coincidence and gives led impulse to close the alternator circuit breaker

 

 

Permissable switching time and adjustable of impulse length

 

Only quick switching circuit breaker should be used ,eg. Air contactors ,magnet operated circuit breakers choose the max permissable switching time of the circuit breaker in thr right hand part of the diagram.

 

(2) frequency regulator :

 

its main function to senses the frequency difference between the incoming machine and the bus bar. It provide correction pulse to the electrical govemer  of the incoming diesel to speed up or slow down the generator  as required for synchronization.

With a large frequency difference. Pulses are given in rapid succession. With little difference pulses are given with long intervals to obtain an optimal speed adjustment.

 

Average pulse duration and interval are adjustable for adaptation to the adjusting speed of the fuel generator. The desired nominal frequency is adjusted by means of the spindle potentiometer. The frequency range is about 45-55 HZ or 55-65 HZ.

 

In a brief the application of this unit is for controlling the frequency of the generating unit. The unit compares the frequency of the sets or bus bar with constant and stable frequency. And provide pulses to the motorized governors of each set accordingly.

 

As example :

 

 Several parallel operation gen-sets have a frequency drop dependent up on their load. Caused by the static droop of the regulator so it provide to occur this drop.

 

(3) frequency control unit :

the frequency control unit is supplied from one phase of each system (one phase bus bar system and one phase alternator). It operate manual or automatic.

This unit compares the two frequencies and gives o/p impulses in the right direction (slower or faster) to the needed governor motor the interval between the impulses is shorter when the difference in frequency is high and longer when the difference is low.

It's recommended that the frequency control unit should be switch off when the generating set is already in parallel to prevent interferences with the load balancing unit.

 

(4) voltage balancing unit :

this unit is used for automatic voltage balancing between three-phase alternators, preferably for paralleling alternators with the mains supply and alternators with-out paralleled excitation systems.

The motorized potentiometer for the voltage setting receives impulses to adjust the required voltage.

 

The unit consists of two measuring circuits, one is the main or reference supply and the other is connected to the system which is to be balanced it is useful to have an additional selector switch "manual-automatic".

 

The unit compares the two supplied voltage and gives outgoing impulses to the motorized potentiometer in case of high voltage difference between two systems the intervals between the impulses are shorter and in case of lower difference between the voltages the intervals are longer. To adept the unit to various motorized potentiometers. The impulses are adjustable using two built-in potentiometers.

 

(5)Power relay :

 

The function of power relay 'LWRI" is the automatically power adaptation for generators. Their power o/p is record via (power) measuring transducers.

With generators running in parallel the LWRI  is used to regulate each of them to have an identical load.

 

(6)Generator power factor regulator :

 

The reactive power of a mains parallel operating generator can reach undesirable value by variations of the mains voltage. At reduced mains voltage the reactive power o/p raises and can lead to our loading of the machine. Mains voltage increase loads to absorption of reactive power and with that undesirable mains load (and reactive power costs might possibly be incurred).    

 

BACK          HOME      

 

تصميم المهندس : محمد صبري محمود فهيم        إستعداد تام لتصميم المواقع    إستعداد تام للعمل داخل أو خارج مصر

E-Mail: Mohamedmsm@Masrawy.com